Technical Data:
- For air conditioners up to 50 kW
- Electrical spec. 230V, 50/60 Hz, 65W
- Pump unit (L x W x H in mm): 185 x 85 x 100
- Max. flow rate (l/h): 350
- Max. delivery height (m): 4
- Tank capacity (l): 0,5
- Alarm switch: max. 230 V, 8 A (ohmic load) NO/NC (normally open/normally closed)
- Operating points* Alarm: max. 55 mm Start: 52 ±1 mm Stop: 24 ±1 mm
- Pressure hose – Ø 8 × 2 mm
Usage
The Eckerle condensate pump EE400M is designed to remove condensate water out of air conditioners, evaporator coils and high efficiency gas furnaces automatically. The pump housing is made from an impact-resistant plastic body against corrosion.
Description
- Extremely quiet running and vibration-free
- Pump encapsulated and liquid cooled
- Protection class IP 55
- Max. medium temperature: 70 °C
- Most compact design
- Pump housing made of glass-reinforced plastic material, including wall mounting accessory
- Separate alarm contact
- Integrated check valve
- Pump unit can be used in an external pan as well. Pan height: min.62 mm, max.70mm